• sns01
  • sns03
  • sns02

VS1-12 Seri Andedan kay la segondè Voltage vakyòm Awondisman brekè

Kout deskripsyon:


Pwodwi detay

Pwodwi Tags

VS1-12 andedan kay la HV sikwi brekè se yon 3-faz AC 50Hz 12kV ekipman switch andedan kay la.

♦ Fason enstalasyon: kalite retrè, kalite fiks, bò monte kalite;

♦ Mekanis opere: mekanis Rating sezon prentan, mekanis pèmanan opere mayetik;

♦ Kalite poto: poto reyini, poto entegre;

♦ Aplikasyon: aparèy KYN28-12, XGN-12.

♦ Ploge Segondè: 58pins, 64pins.

htrh (1)

htrh (2)

Pwodwi Standards

♦ IEC62271-100 High Voltage Switchgear and Controlgear Part 100: AC Circuit-breakers

♦ GB1984 Segondè Voltage AC Awondisman-kasè

♦ GB / T11022 Espesifikasyon Komen pou High-vòltaj switchgear ak Controlgear Standards

♦ JB / T 3855 High Voltage AC Vacuum Circuit-breakers

♦ DL / T402 Specification High-vòltaj AC Awondisman-kasè

Kondisyon anviwònman

♦ Tanperati anbyen: -15 ° C ~ + 40 ° C;

♦ Altitid: <1000m;

♦ Relatif imidite: mwayèn chak jou <95%, mwayèn chak mwa <90%

♦ Entansite tranbleman tè: <8 nivo;

♦ Kote san dife, danje eksplozyon, sal grav, korozyon chimik, osi byen ke Vibration entans.

Main Paramèt teknik

Non

Atik

Inite

Valè

1 Rated vòltaj kV

12

2 1 min frekans pouvwa kenbe tèt ak vòltaj

42

3 Rated enpilsyon zèklè kenbe tèt ak vòltaj

75

4 Rated frekans Hz

50

5 Rated aktyèl Yon

630, 1250, 1600, 2000, 2500,

3150, 4000

6 Rated kout sikwi kase aktyèl la kA

20, 25, 31.5, 40

- Rated kout tan kenbe tèt ak aktyèl

20, 25, 31.5, 40

fa Rated dire sikwi kout s

4

9 Rated valè pik kenbe tèt ak aktyèl la

kA

50, 63, 80, 100

10 Rated sikwi kout fè aktyèl

50, 63, 80, 100

11 Segondè sikwi pouvwa frekans kenbe tèt ak vòltaj (1min) V

2000

12 Rated sèl / tounen-a-tounen labank kondansateur kraze aktyèl la Yon

630/400 (800/400 pou 40kA ak

50kA)

 

Non

Atik

Inite

Valè

13

Rated kondansateur labank fèmen aktyèl aktyèl Yon

12.5

14

Tan ouvèti (rated vòltaj)

ms

20-50

15

Tan fèmen (rated vòltaj)

ms

35-70

16

Lavi mekanik

Fwa

10000

17

Rated aktyèl nimewo kraze

Fwa

10000

18

Rated kout sikwi aktyèl kase nimewo

Fwa

50 (30 pou 40kA; 20 pou 50kA)

19

Deplase ak fiks kontak kimilatif pèmèt epesè mete mm

3

20 Rated fèmen vòltaj opere V

AC / DC110 / 220

21 Rated ouvèti vòltaj opere
22 Rated vòltaj nan motè depo enèji

W

70 (80 ror 40kA ak 50kA)

23 Rated pouvwa nan motè depo enèji
24 Tan depo enèji s

<10

25 Clearance ant kontak ouvè mm

11 ± 1

26 Plis pase vwayaj mm

3.5 ± 0.5

27 Kontakte fèmti rebondisman tan ms

<2 (<3 pou 40kA ak 50kA)

28 Twa faz ouvèti ak fèmen asenkronism ms

<2

29 Mwayèn vitès ouvèti

m / s

0.9-1.2

30 Mwayèn vitès fèmen

m / s

0.5-0.8

31 Main rezistans sikwi kondiktif uQ

<60 (630A) <50 (1250A) <35 (1600-2000A) <25 (pi wo a 2500A)

32 Fèmti presyon kontak nan kontak yo N

2000 ± 200 (20kA)

2400 ± 200 (25kA)

3100 ± 200 (31.5kA)

4250 ± 250 (40kA)

6500 ± 500 (50kA)

33 Rated opere sekans

O-0.3s-CO-180s-CO

O-180s-CO-180s-CO (50kA)

Remak: lè aktyèl se 4000A oswa 5000A, bezwen fòse lè refwadisman.

Jeneral Estrikti Desen ak Enstalasyon Size (inite: mm)

Trase kalite

thr (1)

Lajè kabinè

Rated aktyèl (A)

Rated kout sikwi kase aktyèl (kA)

P H

Yon

B

C

D

E F

G

J

K

L

M

N

R

S

T

650 630

20 〜31.5

150 275 490 502 492

500

433 626

035

280 598 76 78 637 508 202 40
650 1250

20 〜31.5

150 275 490 502 492

500

433 626

049

280 598 76 78 637 508 202 40
800 630

20 〜31.5

210 275 638 652 640

650

433 626

035

280 598 76 78 637 508 277 40
800 1250

20-40

210 275 638 652 640

650

433 626

049

280 598 76 78 637 508 277 40
800 1600

31.5〜40

210 275 638 652 640

650

433 626 055 280 598 76 78 637 508 277 40
1000 630

20 〜31.5

275 275 838 852 838

850

433 626

035

280 598 76 78 637 508 377 40
1000 1250

20 〜40

275 275 838 852 838

850

433 626

049

280 598 76 78 637 508 377 40
1000 1600

31.5-40

275 275 838 852 838

850

433 626

055

280 598 76 78 637 508 377 40
1000 1600-200

31,5 〜40

275 310 838 852 838

850

361 680

079

295 586 77 88 698 536 377

0

1000 2500〜200

31,5 〜40

275 310 838 852 838

850

361 680

0109

295 586 77 88 698 536 377

0

Kalite fiks

s

Lajè kabinè

Ra »yon kouran (A)

P

H

Yon

C

E

G1
G2

J

K

L

650

630-1600

150

275

385

440

580

Mwen

237

455

395

800

630-1600

210

275

520

588

580

II

237

455

410

1000

630 ~ 1600

275

275

720

770

580

II

237

455

410

1000

1600 ~ 5000

275

310

720

770

632

III

252

465

440

Side monte kalite

thr (3)


  • Previous:
  • Pwochen: