Vacuum Interrupter pou disjoncteurs deyò TD-24/630-20 (3D82)

Deskripsyon kout:


Pwodwi detay

Tags pwodwi

svv

Nòt

1. Satisfè oswa depase kondisyon andirans elektrik klas E2 pou devwa autoreclosing pa IEC62271-100 ak GB1984-2003.

2. Karakteristik rated yo dwe bay sou demann.

3. Rated izolasyon valuesrequire extemal insulati on, tankou Sf6, lwil oliv oswa solid materyèl dielectric elatriye.

Espesifikasyon teknik prensipal

Rated Voltage

KV

vennkat

Rated aktyèl

A

630

Rated Frekans

Hz

50

Kout tan pouvwa-frekans reziste vòltaj (1min)

KV

65/79

Rated zèklè enpilsyon reziste vòltaj (pik)

KV

125/145
Rated Kout-Circuit Brenking Kouran

LA

20

Rated pik kenbe tèt ak aktyèl

LA

50

Rated Kout-Circuit fè aktyèl

LA

50

Rated Kout-tan kenbe tèt ak aktyèl

LA

20

Rated dire kout-circ

S

4

Rated Single Capacitor Bank kraze aktyèl

A

400

Rated Back to Back Kondansateur Bank kraze Kouran

A

400

Rated Kout-Circuit fè aktyèl

Fwa

20

Mass nan pati k ap deplase

KG

2.2

Andirans mekanik

Fwa

10000

Kontakte Fòs Fèmen Akòz Bellows ak Atmosfè

N

110±30

Counterforce nan kontak nan Full Stroke

N

190±30

Rezistans chan de kous nan fòs kontak Min.Rated

Kontakte Limit Ewozyon

mm

3

Lavi Depo

Ane

20

Done mekanik nan switch vakyòm ekipe ak entèwonp yo

Clearance ant kontak louvri

mm

12±1

Mwayèn Vitès Ouvèti

m/s

1.4±0.2

Mwayèn vitès fèmen

m/s

0.7±0.2

Rated Kontak Presyon

N

2000±200

Kontakte dire rebondisman nan operasyon fèmen

ms

Soti nan similtane kontak fèmen ak operasyon

ms

Maksimòm detant pandan ouvèti

mm


  • Previous:
  • Pwochen: