Vacuum Interrupter pou disjoncteurs deyò TD-12/630-25 (2D89)

Deskripsyon kout:


Pwodwi detay

Tags pwodwi

rht

Nòt

1. Satisfè oswa depase kondisyon andirans elektrik klas E2 pou devwa autoreclosing pa IEC62271-100 ak GB1984-2003.

2. Karakteristik rated yo dwe bay sou demann.

3 .Rated izolasyon valuesrequire extemal insulati on, tankou Sf6, lwil oliv oswa solid materyèl dielectric elatriye.

Espesifikasyon teknik prensipal

Rated Voltage

KV

12

Rated aktyèl

A

630

Rated Frekans

Hz

50

Kout tan pouvwa-frekans reziste vòltaj (1min)

KV

48

Rated zèklè enpilsyon reziste vòltaj (pik)

KV

75

Rated Kout-Circuit Brenking Kouran

LA

25

Rated pik kenbe tèt ak aktyèl

LA

63

Rated Kout-Circuit fè aktyèl

LA

63

Rated Kout-tan kenbe tèt ak aktyèl

LA

25

Rated dire kout-circ

S

4

Rated Single Capacitor Bank kraze aktyèl

A

630

Rated Back to Back Kondansateur Bank kraze Kouran

A

400

Rated Kout-Circuit fè aktyèl

Fwa

20

Mass nan pati k ap deplase

KG

0.6

Andirans mekanik

Fwa

10000

Kontakte Fòs Fèmen Akòz Bellows ak Atmosfè

N

80±30

Counterforce nan kontak nan Full Stroke

N

130±30

Rezistans chan de kous nan fòs kontak Min.Rated

Kontakte Limit Ewozyon

mm

3

Lavi Depo

Ane

20

Done mekanik nan switch vakyòm ekipe ak entèwonp yo

Clearance ant kontak louvri

mm

9±1

Mwayèn Vitès Ouvèti

m/s

1.1±0.2

Mwayèn vitès fèmen

m/s

0.7±0.2

Rated Kontak Presyon

N

1800±200

Kontakte dire rebondisman nan operasyon fèmen

ms

Soti nan similtane kontak fèmen ak operasyon

ms

Maksimòm detant pandan ouvèti

mm